Aboveground horizontal tanks

Aboveground tanks double-skinned

Purpose:

Storage of flammable and non-flammable, materials harmful to the environment with a density to 1,1 kg/dm3 for EN 12285 class A and to 1,9 kg/dm3 for tanks
EN 12285 class B and DIN6616.

Tank characteristics:

  • Single or multi-chamber tank
  • Working pressure: max 0,5 bar
  • Working temperature: from -20°C to + 50°C

Outer surface:

Abrasive grit-blasted to grade Sa 2,5 according to PN-ISO 8501-1 and painted in C3 standard or higher.

Standard Equipment:

  • Manhole DN600 with gasket
  • Steel supports for EN-tanks: 1,9 N/mm2 for DIN 6616-tanks
    0,15 N/mm2)
  • transport grips
  • ladder, platform, railing
  • Filling pipe, suction pipe, venting pipe

Optional Equipment:

  • Overfill valve, venting valve, de-watering pipe
  • System and control pipes
  • Contents measuring

Safety:

Double skinned above ground steel tanks meet all the requirements for the storage of liquids harmful to groundwater and environment. The space between the internal and external wall is monitored.

Basic technical data:

Volume Diameter Length Manhole Weight Wall thickness
class A class B class A class B
V Dz Lo DN G G S1 S2 S1 S2
[m3] [mm] [mm]l [mm] [kg] [kg] [mm] [mm] [mm] [mm]
3
5
7
10
13
16
1600
1600
1600
1600
1600
1600
2040
3040
3840
5540
7040
8540
600 946
1266
1518
2051
2513
2993
1020
1340
1590
2126
2592
3069
5 3 5 3
10
13
16
20
25
30
36
2000
2000
2000
2000
2000
2000
2000
3660
4660
5660
6810
8660
10160
11960
600 2143
2588
3044
3567
4394
5133
5943
2335
2780
3237
3761
4588
5328
6138
6 3 6 3
20
25
30
40
50
60
70
2500
2500
2500
2500
2500
2500
2500
4800
5800
6800
8800
10800
12800
14800
600 3838
4456
5068
6373
7599
8915
10136
4653
5335
6010
7442
8796
10239
11586
6 4/5 7 4/5
40
50
60
70
80
100
2900
2900
2900
2900
2900
2900
6900
8400
9900
11400
12900
15900
600 6722
7990
9175
10347
11612
13974
9016
10504
11909
13301
14786
17588
7 4/5 9 4/5